Plug-in solar is now legal to use in Great Britain. SI 2026/848 came into force on 27 August 2026 and Ofgem has approved the G98 connection changes — only kits listed on the ENA Type Test Register may be used, and Northern Ireland is not covered. Read the UK legal status

MyPlugInSolar

Products & compliance

The plug-in solar safety study explained

Before plug-in solar became legal in Great Britain, the government had six devices tested on circuits built to mimic British homes. This is what that study found, where products fell short, what it did not test, and how the rules answered it.

Written and edited by Christopher Panteli

Christopher is the founder and editor of MyPlugInSolar. He oversees the site’s research standards, data tools and editorial process. He is not an electrician or solar installer, and specialist technical claims are sourced from official documentation or reviewed by appropriately qualified professionals.

Legal to use in Great Britain since 27 August 2026

Plug-in solar has been legal to use in Great Britain since 27 August 2026, when SI 2026/848 came into force alongside Ofgem-approved changes to the G98 connection code — provided the kit is listed as compliant on the ENA Type Test Register. Northern Ireland is not covered. See the legal status for the current position and sources.

Why the study was done

Before changing the rules, the government wanted UK evidence that a solar panel plugged into an ordinary socket is safe in a British home. British wiring differs from Germany’s, where balcony solar is common: ring circuits, fused BS 1363 plugs and a mix of old and new protective devices. The Plug-in solar electrical safety study is that evidence. It was commissioned and funded by the Department for Energy Security and Net Zero (DESNZ), carried out by the engineering consultancy Arceio with the laboratory Eurofins E&E UK, and published on GOV.UK on 16 June 2026, the day the government opened its plug-in solar consultation.

The report notes that its views are Arceio’s own and do not necessarily reflect the government’s. Its question was narrow: can plug-in devices be used safely when connected to existing sockets “without modification to fixed wiring, protective devices, or consumer units”?

What was tested, and how

The study tested a “purposive engineering sample of six commercially available devices”, chosen to cover different inverter designs, export ratings and form factors, “broadly within the 400 W to 800 W AC export range”. The devices are anonymised, and the report says its findings are “evidence of category behaviour rather than … product approvals or rankings”. Six devices is not a market survey, and the report says so.

Testing ran in UKAS-accredited laboratory conditions on rigs built to represent UK homes: a ring circuit and radial spurs, Type A and Type AC protective devices (RCBOs), new and aged sockets, metal and plastic sockets, and deliberately poor conditions such as worn contacts, a coiled extension lead and heavy household loads on the same circuit. Most tests used programmable power supplies in place of panels, so results could be repeated, with some outdoor tests on real panels.

What the tests found

The report’s own summary is that the devices “can demonstrate safe and technically coherent behaviour within the tested no-modification boundary”, and that “No electrical hazard was identified as a result of socket connected plug-in PV operating within the tested export envelope.” The detail, test area by test area:

Principal outcomes of the Plug-in solar electrical safety study (DESNZ, June 2026), summarised from section 4 and Table 4.3 of the report.
Test areaWhat the study found
Heat at the plug and socketStable on all six devices under sustained full output. Inverter casings ran at about 45 °C to 54 °C; plug and socket temperatures stayed below the limits used.
Circuit protection (RCBOs)Protective devices tripped in every completed fault event. 26 of the measured events were within the 40 ms benchmark; one was not, at 89 ms, for one device on a Type AC ring circuit.
Ring circuits and two-way currentNo hotspots on wiring, sockets or plugs, including with about 2 kW of household load running alongside full export.
Short circuitsProtection operated correctly and the devices restarted normally once the fault was cleared.
Switching off when the mains goesEvery device that completed the test disconnected within G98’s 500 ms limit, in about 7 ms to 68 ms.
High temperaturesBroadly stable. One device’s mains cable sheath shrank during prolonged high-temperature exposure.
Electrical interference (EMC)Conducted emissions at full power exceeded the strict Class B limit for homes on the tested samples, though household appliances alone also exceeded it. Harmonic currents stayed within limits.
Voltage and frequency extremesStable within the normal ranges. At the extremes, several devices did not switch off at the G98 thresholds; some kept running above 273 V, and one stayed on past the upper frequency limit.
Export limitSeveral devices stayed below their declared maximum; two 400 W devices went over 400 W during parts of the voltage sweep. None approached the G98 single-phase threshold.

Not every device completed every test. One was left out of some tests because its panel-side connector was already damaged, and another needed a Wi-Fi connection to start that could not be made inside the shielded laboratory.

Where products varied

The study is careful to separate safety from consistency. Its words: “The findings support a clear distinction between general operational stability and full conformity consistency.” The areas where products differed were interference at full power, how devices behaved at the edges of the voltage and frequency range, and whether they kept to their own declared export limit. It does not call these evidence of widespread unsafe behaviour, but concludes that “product quality is not uniform across the market and that a UK product specification would be beneficial”.

On interference, the report found that existing test standards do not require emissions to be measured at maximum output, so a product’s existing certificates “may not reflect worst case in-use conditions”.

What the study did not cover

The study set out what it did not cover, and these are the honest limits of what it can tell you:

  • effects of many devices on the same street or network, such as transformer loading;
  • long-term wear of sockets, plugs, leads and inverters;
  • battery-integrated or hybrid systems;
  • any set-up that needs new wiring or electrical work.

It also stressed that safety depends on the home as well as the product: “deployment safety depends not only on the characteristics of the device itself, but on the condition of the receiving installation and the behaviour of the consumer.”

How the product specification answers it

The study made nine recommendations. The interim product specification (version 2), which SI 2026/848 gives legal effect, answers most of the technical ones directly:

Study recommendations set against the interim product specification, version 2 (DESNZ, July 2026).
The study recommendedWhat the specification requires
A defined qualifying product categoryManufacturers must register devices on the ENA Type Test Register and have them confirmed as compliant before placing them on the market.
Clear export and disconnection requirementsMaximum apparent power of 800 VA and current of 3.5 A; the specification points to G98’s interface and loss-of-mains protection, which disconnects at voltage and frequency extremes and when the mains is lost.
Interference tested at full power, to the Class B limit for homesEmissions “shall be tested in accordance with BS EN IEC 61000-6-3” at the maximum power the inverter can deliver.
A fused, moulded UK plug supplied with the kitA non-rewireable moulded BS 1363 plug with partially insulated pins and a fuse of no more than 5 A.
A weatherproof socket for outdoor connectionWhere the plug and socket are outside, a socket rated IP55 or better (the study suggested IP56).
Guidance on sockets, leads and adaptorsInstructions must say extension cables, multi-way adaptors, RCD adaptors and travel adaptors are not permitted, and the device must carry that warning.
A simple registration stepNotifying the network operator of connection is mandatory; see G98 notification.

The specification goes further than the study in places: it limits panels to 2,000 W, excludes battery systems, and tells manufacturers to advise a professional check of the wiring above 960 W of panels. The study’s other recommendations, on market surveillance and monitoring, fall to regulators rather than to the product.

What it means for you

  • Buy a listed kit. The study found products vary, and the register is how the UK filters them: check the exact kit on the ENA register.
  • Plug straight into a sound wall socket. No extension lead, adaptor or travel plug, and a weatherproof socket outdoors. If the socket is old, scorched or loose, get it checked first; see do you need an electrician.
  • Know your protective device. The one slow trip was on a Type AC device; our RCD guide explains the types and how to tell which you have.
  • Notify your network operator. See G98 notification explained.

Frequently asked questions

Did the government’s safety study find plug-in solar safe?
Within the conditions it tested, yes. The study found that plug-in devices on UK socket circuits behaved safely: protection kept working, devices switched off promptly when the mains was lost, and no electrical hazard was identified within the tested export range. It also found products were not uniform, and recommended a UK product specification.
How many devices did the study test?
Six commercially available devices, rated broadly 400 W to 800 W, chosen to cover different inverter designs. They are anonymised in the report, and the study is not a ranking or approval of any product.
Did the study test extension leads?
Yes, as a foreseeable misuse. It did not find a new hazard from the devices under the scenarios tested, but said that did not make those conditions risk-free. The UK product specification does not permit extension cables, multi-way adaptors, RCD adaptors or travel adaptors.
What did the study not cover?
Effects across a whole network, long-term wear of sockets, plugs and inverters, battery or hybrid systems, and any set-up needing electrical work.

Sources

Estimate your solar potential

See how much electricity a small system could generate at your postcode, and the indicative bill saving.

Open the calculator